Detail publikace
Time Synchronization in Power-line Communication
ŠŤASTNÝ, L. FRANEK, L. JIRGL, M. MIŠÍK, Š. BRADÁČ, Z.
Originální název
Time Synchronization in Power-line Communication
Anglický název
Time Synchronization in Power-line Communication
Jazyk
en
Originální abstrakt
This paper proposes possible way how to realise time synchronization for Smart Grid devices over power-line communication (PLC). Time synchronization methods like 1- PPS, IRIG-B, GPS time or IEEE1588 are well known and used generally in Smart Grids, but not suitable for most devices with PLC. PLC channel is considered as difficult due to strong interferences, slow communication speeds and variable topology. Proposed solution for low-voltage segment uses significant event on line, zero-crossing for synchronization purpose.
Anglický abstrakt
This paper proposes possible way how to realise time synchronization for Smart Grid devices over power-line communication (PLC). Time synchronization methods like 1- PPS, IRIG-B, GPS time or IEEE1588 are well known and used generally in Smart Grids, but not suitable for most devices with PLC. PLC channel is considered as difficult due to strong interferences, slow communication speeds and variable topology. Proposed solution for low-voltage segment uses significant event on line, zero-crossing for synchronization purpose.
Dokumenty
BibTex
@inproceedings{BUT114590,
author="Ladislav {Šťastný} and Lešek {Franek} and Miroslav {Jirgl} and Štefan {Mišík} and Zdeněk {Bradáč}",
title="Time Synchronization in Power-line Communication",
annote="This paper proposes possible way how to realise time synchronization for Smart
Grid devices over power-line communication (PLC). Time synchronization methods like 1-
PPS, IRIG-B, GPS time or IEEE1588 are well known and used generally in Smart Grids,
but not suitable for most devices with PLC. PLC channel is considered as difficult due to
strong interferences, slow communication speeds and variable topology. Proposed solution for
low-voltage segment uses significant event on line, zero-crossing for synchronization purpose.",
booktitle="13th IFAC Conference on Programmable Devices and Embedded Systems - PDeS 2015",
chapter="114590",
doi="10.1016/j.ifacol.2015.07.012",
howpublished="online",
number="13",
year="2015",
month="may",
pages="83--88",
type="conference paper"
}