Detail publikace

A Flickermeter based on Voltage Peak Detection Method - Part II: Standardized Verification and Performance in Real Deployment

ŠLEZINGR, J. DRÁPELA, J.

Originální název

A Flickermeter based on Voltage Peak Detection Method - Part II: Standardized Verification and Performance in Real Deployment

Anglický název

A Flickermeter based on Voltage Peak Detection Method - Part II: Standardized Verification and Performance in Real Deployment

Jazyk

en

Originální abstrakt

The paper deals with a standardized verification proce-dure applied on an alternative digital time domain based flickermeter type having response to high-frequency inter-harmonics and its performance testing in real deployment. The flickermeter utilizes a Voltage Peak Detection (VPD) method and the signal processing is realized using virtual instrumentation in LabView together with a NI cDAQ plat-form. Standardize verification is performed by means of tests and requirements defined in the standard IEC 61000-4-15. The performance in the real deployment was tested by a set of tests focused mainly on cumulative disturbances includ-ing interharmonic distortion and by a long time measure-ment in the supply network with the simultaneous deployment of other types of flickermeters. The results of all measurements are compared and discussed.

Anglický abstrakt

The paper deals with a standardized verification proce-dure applied on an alternative digital time domain based flickermeter type having response to high-frequency inter-harmonics and its performance testing in real deployment. The flickermeter utilizes a Voltage Peak Detection (VPD) method and the signal processing is realized using virtual instrumentation in LabView together with a NI cDAQ plat-form. Standardize verification is performed by means of tests and requirements defined in the standard IEC 61000-4-15. The performance in the real deployment was tested by a set of tests focused mainly on cumulative disturbances includ-ing interharmonic distortion and by a long time measure-ment in the supply network with the simultaneous deployment of other types of flickermeters. The results of all measurements are compared and discussed.

Dokumenty

BibTex


@inproceedings{BUT92251,
  author="Jan {Šlezingr} and Jiří {Drápela}",
  title="A Flickermeter based on Voltage Peak Detection Method - Part II: Standardized Verification and Performance in Real Deployment",
  annote="The paper deals with a standardized verification proce-dure applied on an alternative digital time domain based flickermeter type having response to high-frequency inter-harmonics and its performance testing in real deployment. The flickermeter utilizes a Voltage Peak Detection (VPD) method and the signal processing is realized using virtual instrumentation in LabView together with a NI cDAQ plat-form.  
Standardize verification is performed by means of tests and requirements defined in the standard IEC 61000-4-15. The performance in the real deployment was tested by a set of tests focused mainly on cumulative disturbances includ-ing interharmonic distortion and by a long time measure-ment in the supply network with the simultaneous deployment of other types of flickermeters. The results of all measurements are compared and discussed.",
  address="Brno University of Tecnology",
  booktitle="Proceedings of the 13th International Scientific Conference Electric Power Engineering 2012",
  chapter="92251",
  edition="Vol. 1",
  howpublished="print",
  institution="Brno University of Tecnology",
  year="2012",
  month="may",
  pages="443--448",
  publisher="Brno University of Tecnology",
  type="conference paper"
}